The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management-including low-voltage protection and optional load disconnect-plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Envoyer Obtenez Prix
| Caractéristiques d'environnement | Des conditions de fonctionnement | Conditions de transport | Conditions de stockage | Normes applicables | Remarques | |||
| Catégories | Paramètre | Unité | ||||||
| Conditions climatiques | Température | Basse température | ℃ | - 33 | - 40 | - 40 | YD/T 1058-2000 Clauses 4.1.1 et 4.1.2 | Démarrage à pleine charge à −40℃ ; réduction linéaire de 20 % de +55 à +65℃. |
| Température élevée | ℃ | 65 | 70 | 70 | ||||
| Changement de température | ℃ / min | / | 1 | / | ETS 300 019-2-2 T2.3 | |||
| Température ambiante de fonctionnement | ℃ | -33-65 | température de fonctionnement extrême à pleine charge | |||||
| La température de stockage | ℃ | -40-70 | ||||||
| Humidité | Humidité relative | % | 5-90 | 90 (40±2℃) | / | YD/T 1058-2000 Article 4.1.3 | Short-term test: 0-95%, max 95%, non-condensing | |
| Condensation | Oui Non | Non | Non | Oui | ||||
| pression atmosphérique | Basse pression | kPa | 86 | 70 | 70 | YD/T 1058-2000 Article 4.1.4 | Tests de modules uniquement | |
| Haute pression | kPa | 106 | 106 | 106 | ||||
| Altitude | m | ≤ 4000 | Au-delà de 2000 m, réduire la température de 0.5 °C par tranche de 100 m supplémentaires. | |||||
Remarque : Les spécifications peuvent être modifiées sans préavis afin d'améliorer le produit. Fiche technique
Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring
Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX
High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms
Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing
Equipotential design across the cabinet improves EMC and lightning protection
Il convient à divers scénarios de consommation d'énergie tels que les bâtiments résidentiels et les immeubles de bureaux commerciaux.
Nous nous engageons à fournir un soutien rapide et professionnel pour garantir que vos besoins énergétiques soient toujours satisfaits avec le plus haut niveau de service.
Nous sommes là pour répondre à vos questions et vous proposer les solutions énergétiques les mieux adaptées à vos besoins.